Booster Pump Pressure Control Project in Melbourne: Local Indication and Alarm Contacts
In 2024, a Melbourne manufacturer of packaged booster-pump systems contacted Dongya Instrument while revising a pump-control panel used on commercial water-supply equipment. The panel already displayed pressure through a mechanical gauge. A separate switch supplied the low-pressure and high-pressure signals. The manufacturer wanted its next production version to keep an easy local reading while simplifying the number of pressure devices it had to mount, wire and stock.
The question was whether one electric-contact gauge could serve the required indication and limit-signal functions without creating nuisance switching when the pumps started. We worked from the customer’s piping and wiring drawings rather than treating an electric-contact gauge as a drop-in replacement for every sensor or controller.
Project at a glance
| Customer | Booster-pump equipment manufacturer, Melbourne, Australia |
|---|---|
| Application | Local pressure reading and limit contacts on a packaged water-supply skid |
| Operating band | Approximately 0.45–0.65 MPa during normal operation |
| Required limits | Low-pressure signal at 0.35 MPa; high-pressure signal at 0.80 MPa |
| Selected instrument | YNXC-100 vibration-resistant electric-contact pressure gauge, 100 mm dial, 0–1.6 MPa range |
| Connection and circuit | M20 × 1.5 process connection; contacts wired to an interposing relay and control panel |
| Supply | 16 pilot gauges followed by a 500-piece first order |

What the pump builder needed to control
The customer’s existing panel used a gauge for technicians and a separate pressure switch for the controls. That arrangement worked, but it added a second process connection and another part number to each skid. The manufacturer wanted operators to see the pressure and the alarm setpoints at the same location. It also wanted the control contacts to signal a relay rather than carry the pump-motor load.
There was a complication. Pressure moved briefly during pump start and changeover, and the customer’s first wiring concept would have acted on every short contact transition. We asked the controls team for the pressure trend, the required low and high thresholds, the contact-load details and the panel logic. We also checked the connection and mounting orientation. A gauge could provide the contact signal, but the system controller still had to decide when that signal represented a sustained condition requiring action.
How we specified the gauge and control interface
We proposed the YNXC-100 vibration-resistant electric-contact pressure gauge. Dongya’s YNXC range is designed for pressure indication with electrical contacts in applications where vibration resistance is needed. The 100 mm format gave the panel technician a visible local scale, while adjustable contacts provided the two agreed pressure-limit signals.
We selected the 0–1.6 MPa range from the customer’s operating and alarm brief, then put the 0.35 MPa low and 0.80 MPa high settings on the sample approval sheet. The process connection was M20 × 1.5 to match the skid drawing. The buyer also specified dial units, cable-entry orientation and the contact-terminal identification required by its panel shop. Those details were checked before sampling so a gauge that passed a pressure test would also fit the finished enclosure.
The contact circuit was agreed separately from the pressure scale. We asked the panel builder to verify the instrument’s contact rating against the relay input and to use an interposing relay for the control circuit. The gauge contacts were not specified to switch a pump motor directly. We also agreed that start-up filtering and alarm delays belonged in the customer’s control logic. This kept a momentary pressure dip during pump changeover from becoming an unnecessary shutdown.
Pilot check: pressure, contacts and panel behavior

We supplied 16 pilot gauges for bench and skid checks. The customer checked pressure indication at several points across the intended operating range, then moved pressure through each contact setting to verify the low and high signals at the panel. The same tests were repeated after installation on the packaged pump units, with the pumps starting, stopping and changing duty.
The first on-skid test showed the exact reason the control drawing mattered: a brief start-up pressure dip crossed the low setting even though the system recovered immediately. The controls team added a short confirmation delay in the panel logic and reran the test. The low-pressure alarm then responded to a sustained low-pressure condition without reacting to that normal transient. The gauge itself remained a local indicator and contact device; the panel performed the decision and switching functions.
After a four-week evaluation, the manufacturer approved the gauge drawing, setpoint record and terminal layout for its next build. The pilot established fit and control behavior under the agreed test conditions. It was not treated as proof that every pump station or electrical environment would require the same settings.
Production order and batch checks
The customer placed a 500-piece first order against the approved specification. Its purchase documents listed the pressure range, connection, mounting arrangement, dial, contact settings, terminal identification, packaging and required inspection record. That information mattered to both the pump assembly line and the spare-parts team. A replacement gauge with the correct model but different contact setting would not be the same part.
Our production process included component checks, assembly inspection, finished appearance and zero-position checks, indication checks on rising and falling pressure, sealing checks and record retention. For this order, the customer’s receiving inspection also used the approved setpoint and terminal checklist. The gauges were packed by the agreed part number so the panel shop could issue the correct variant to each build.
Result for the manufacturer and its distributors
The manufacturer left the pilot with one defined pressure instrument for local indication and two limit signals on the covered booster-pump skid. Its panel logic handled transient filtering, while the gauge and contact settings were documented for repeat orders. That reduced the number of pressure-device variants the buyer had to manage and gave its distributors a clear replacement specification.
The result depended on the complete system design. An electric-contact gauge supplies contact states; it does not replace a controller, prove an electrical load is within rating, or guarantee that a setpoint chosen for one skid suits another. The useful purchasing lesson was to approve the mechanical connection, pressure range, contact circuit and panel logic together before a bulk order.
Planning a pump-control gauge order?
Send us your normal and maximum pressure, low and high setpoints, process medium, connection, mounting drawing, contact load, relay or PLC input details, vibration conditions and expected quantity. We can review the gauge configuration and sample requirements with your engineering team. Explore our electric-contact pressure gauge range or contact Dongya with your panel drawing.